UPS calculator for a server room
Add your equipment and choose the battery runtime — the calculator suggests a UPS rating with headroom, the battery energy and the input current.
Equipment
The default power is a planning estimate, not the power supply maximum. For a more accurate figure, use iLO or iDRAC (the Power section), HPE Power Advisor or the Dell Enterprise Infrastructure Planning Tool.
Parameters
How the calculator works
- The load is a sum: quantity × power of each device in watts.
- 20–30% headroom covers load growth and inrush currents. Running a UPS close to 100% load is not an option: it shortens the runtime and the battery life.
- The UPS apparent power in volt-amperes = load with headroom / UPS power factor. The calculator picks the nearest size that has enough of both VA and W.
- Battery energy ≈ load × time / inverter efficiency (0.9) with a 25% reserve for battery aging and cold. This is an estimate: the runtime of a specific model is given in its runtime table.